top of page



PMC AB
Ablation fire retardant coating for electrical cables
RENITHERM® PMC AB is a solvent-free coating
for electrical cables laid horizontally or vertically
Characteristic



Solvent Free
Free from halogens



resistant to oil and
petrol spills
weatherproof
and
UV resistant
free from
plasticizer


ageing resistant
viscoelastic, abrasive resistant



no asbestos
non toxic
decontaminate
temperature resistant
down to
– 40 °C after application
for indoor and outdoor
application
Tested and approved by Germanischer Lloyd acc.
to IEC 60331-21:1999
and
IEC 60332-3
Application
Recommended conditions for application:
-
material and air temperature > +5 °C, humidity < 80 %
-
Renitherm® PMC AB has to be stirred thoroughly before use by a slow running stirrer
-
application by brush, roller, or airless spraying (0.023”– 0.025”)
Coverage rate
-
approx.1.35 mm
-
wet = 1.00 mm
-
dry = 1.82 kg/sqm
-
thinning with water, maximum 3 %


Drying times
The drying time depends on temperature and humidity.
At a temperature of approx. +20 °C and humidity of approx. 65 %
the drying time is as follows:
1. dust-dry approx. 3 hrs
2. touch dry approx. 6 hrs
3. fully cured approx. 24 hrs
Environment, Health, and Safety Data
-
no danger classification
-
keep off food
-
take notice of the material
-
safety data sheet
bottom of page